DEPARTMENT  OF  THE  ARMY 

Sacramento  Oietnct,  COFVS  OF  ENGtNEERS 
Wiliams  Resident  Office 
1 7800  S Camp  waiiams 
Riverton,  UT  84065 


October  28.  2013  C-0722 

Subject;  Contract  No.  W9120R‘10'C-0094;  Utah  Data  Center.  Camp  Williams,  Utah 
01  - Life  Safety  Inverter  Fire  Alarm  System  Connections 

Balfour  Beatty/OPR/Big-D 

404  West  400  South 

Salt  Lake  City,  Utah  64101  -1106 

Gentlemen, 

The  purpose  of  this  letter  is  to  serve  BDB  notice  that  the  current  installation  and 
monitoring  of  the  Life  Safety  Inverters  (LSI’s)  is  not  compliant  with  contract  requiremems 
and  to  direct  BDB  to  move  forward  with  completing  the  LSI  installations. 

Per  FEES-11. 1.1  (12).  The  inverter  shall  be  connected  to  the  fire  alarm  system  in 
order  to  transmit  a status  report."  The  fire  alarm  system  currently  monitors  the  status  of 
a smoke  detector  installed  in  the  LSI  enclosure.  However,  the  Government's  position  is 
that  monitoring  the  status  of  a smoke  detector  in  the  LSI  is  not  equivalent  to  monitoring 
status  of  the  LSI  itself  and,  therefore,  the  Contract  requirement  referenced  above  is  not 
being  satisfied. 

Per  FEES-02,  1 .7  (4),  "A  thermostat  with  transmitter  shall  also  be  provided  in  the 
inverter  room  and  be  connected  to  the  SCADA  system."  The  temperature  transmitters 
installed  in  the  LSI  rooms  are  currently  only  connected  to  the  EMCS  system,  and  not  the 
SCADA  system  as  required  by  Contract.  The  Government's  position  is  that  connecting 
the  room  temperature  transmitter  to  the  EMCS  system  is  not  equivalent  to  connecting  to 
the  SCADA  system  and,  therefore,  the  Contract  requirement  referenced  above  is  not 
being  satisfied 

BDB  is  hereby  directed  to  complete  the  LSI  installations  in  accordance  with  Contract 
requirements. 

If  you  have  any  other  questions  or  concerns,  please  contact^^^^^  at 
(601)302-5040. 


Sincerely, 


Administrative  Contracting  Officer 
Williams  Resident  Office